EUCHNER – More than safety.
EUCHNER – More than safety.

ESM-BA301 (Order no. 085613)

Basic device ESM-BA3.., 3 safety contacts, 1 auxiliary contact, cat. 4

  • ESM-BA.. Use up to category 4 according to EN ISO 13849-1
  • LED status indicators
  • 1-channel or 2-channel control
  • 3 redundant safety contacts
  • 1 auxiliary contact (monitoring contact)
  • Short circuit and earth fault/ground fault monitoring
ESM-BA301 (Order no. 085613)

Description

Relay outputs

The outputs are electrically decoupled and of redundant design.

Connection options

By using suitable wiring, the following functions can be selected:

  • Relay start with automatic start or a start button.
  • Monitoring of downstream relays or contactors.
  • Simultaneity monitoring to monitor safety components over time.
  • Relay start using a monitored start button.
  • Short circuit monitoring to detect short circuits between the connecting cables and to shut down the outputs or prevent relay starting if necessary.
  • Earth fault/ground fault monitoring to detect short circuits between the connecting cables and earth or ground and to shut down the outputs or prevent relay starting if necessary.

Auxiliary contacts

The relays in the series ESM-BA3.. are available with electrically separate normally closed contacts and auxiliary contacts.

Connection terminals

Optionally, the ESM-BA... devices are also available as version with plug-in connection terminals.

Dimension drawing
Dimension drawing
Wiring diagram
Wiring diagram

Dimensional drawings

Dimensional drawings

Connection examples

Connection examples

Technical data

Approvals

Zulassung EACZulassung TÜV Rheinland, BMPB mit ZG: Product Safety, Functional SafetyZulassung c_UL_us LISTED

Mechanical values and environment

Housing material
Housing Polyamide PA6.6
Weight
Net 0,23 kg
Ambient temperature -15 ... 40 °C (If several ESM-BA3.. devices are closely spaced under load, the max. cumulative current at the ambient temperature of T=20°C is 9A; at T=30°C is 3A; at T=40°C is 1A. If these currents are exceeded, a spacing of 5mm between the devices must be observed.)
Degree of protection IP20
Mechanical life
operating cycles 10 x 106
Contact material AgSnO2
Mounting method Mounting rail 35mm according to DIN EN 60715 TH35
Connection Connection terminals
Length of control cable
With conductor cross-section 0.75mm2 1000 m
Safety contacts 13/14, 23/24, 33/34
Number of safety contacts 3
Auxiliary contacts 41/42
Number of auxiliary contacts 1

Electrical connection ratings

Operating voltage
AC/DC 24 V -10% ... +10% (All the electrical connections must either be isolated from the mains supply by a safety transformer according to EN 61558-2-6 with limited output voltage in the event of a fault, or by other equivalent isolation measures.)
Rated insulation voltage Ui
AC 250 V
Rated impulse withstand voltage Uimp
Leakage path/air gaps 4 kV
Overvoltage category according to IEC EN 60664-1 3
Reverse polarity protection
On version UB =24V DC
Rated supply frequency 50 ... 60 Hz
Connection rating
at 24 V DC 2,3 W
Degree of contamination (external, according to EN 60947-1) 2
Connection cross-section 0,14 ... 2,5 mm² (Connection terminal (size))
Test voltage
Control system/contacts 2,5 kV
Control voltage
On S11 24 V 18,6 ... 26 V Start button
Control current
S11...S14 60 mA
LED indicator 2 status displays (green) for relays K1 and K2
Safety contacts 13/14, 23/24, 33/34
Type of output
NO Relay contacts, floating and positively driven (redundant) (Positively driven relay according to EN 50205)
Switching voltage
AC max.250 V
DC max.24 V
Switching current
at 24V min.5 mA
Cumulative current max.15 A For all contacts (If several ESM-BA3.. devices are closely spaced under load, the max. cumulative current at the ambient temperature of T=20°C is 9A; at T=30°C is 3A; at T=40°C is 1A. If these currents are exceeded, a spacing of 5mm between the devices must be observed.)
Fusing
External contact fuses (safety circuit) according to IEC 60269-1 10A gG
Utilization category acc. to EN 60947-5-1
AC-15 3A , 250V
DC-13 3A , 24V
AC-12 8A ohmic load, 250V (6 operating cycles/min.)
DC-12 8 A ohm resistive load, 40 V (6 operating cycles/min.)
Breaking capacity according to UL 8A 250V AC / 3A 24V DC per contact
Auxiliary contacts 41/42
Type of output
NC Relay contacts, floating
Utilization category acc. to EN 60947-5-1
AC-12 2A ohmic load, 250V
DC-12 2 A ohm resistive load, 40V
Breaking capacity according to UL 2A, 250V AC / 2A, 24V DC per contact

Other

In compliance with EN ISO 13849-1: 2015; EN 62061: 2005 + AC: 2010 + A1: 2013 + A2: 2015; EN 50581: 2012 (RoHS)

Reliability values according to EN ISO 13849-1

Performance Level PL e (This value is dependent on the number of switching cycles and the switching current.)
Category 4 (This value is dependent on the number of switching cycles and the switching current.)
PFHD 1.2 x 10-8 (This value is dependent on the number of switching cycles and the switching current.)
Number of switching cycles
≤ 0.1 A at 24 V DC max.500000 1/Jahr
≤ 1 A at 24 V DC max.350000 1/Jahr
≤ 2 A at 24 V DC max.100000 1/Jahr
Mission time 20 y (This value is dependent on the number of switching cycles and the switching current.)

Downloads

Complete package

Download all important documents with a single click.

Content:

  • The operating instructions and any additions to the operating instructions or brief instructions
  • Any data sheets to supplement the operating instructions
  • The declaration of conformity
Download Complete Package (ZIP, 2,9 MB)

Single Documents

Other Documents

Ordering data

Ordernumber 085613
Item designation ESM-BA301
Gross weight 0,21kg
European Article Number (EAN) 4047048005990
Customs tariff number 85364110
ECLASS 27-37-18-19 Device for monitoring of safety-related circuits

Technical support

Technical support
Do you have technical questions about our products, their possible use or applications? Our experts will be happy to help.

EUCHNER (UK) Ltd.
+44 114 2560123
sales(at)euchner.co.uk

EUCHNER USA Inc.
+1 315 701-0315
info(at)euchner-usa.com

Cookie notice

We use technically necessary cookies that are essential for the operation of the website. In addition, we use a statistics cookie to analyze the use of our website and to continuously improve our offer. You can decide for yourself whether you wish to consent to the use of the statistics cookie. Further information can be found in our privacy policy.