Contact expansion ESM-TE.., 3 safety contacts, 1 auxiliary contact, time-delay, cat. 3
- Use up to category 3 according to EN ISO 13849-1
- LED status indicators
- Control using safety relays
- 3 redundant time-delayed safety contacts
- Fixed time delay of 0.5 s
- 1 auxiliary contact
- Earth fault/ground fault monitoring can be selected
Description
Relay outputs
The outputs are electrically decoupled and of redundant design.
Connection
By using suitable wiring the following function can be selected:
- Earth fault/ground fault monitoring to detect short circuits between the connecting cables and earth or ground and to shut down the outputs or prevent relay starting if necessary.
Dimensional drawings
Connection examples
Technical data
Approvals
Mechanical values and environment
Housing material | |
Housing | Polyamide PA6.6 |
Weight | |
Net | 0,23 kg |
Ambient temperature | |
At UB = 24V AC | -15 ... 40 °C |
At UB = 24V DC | -15 ... 60 °C |
Degree of protection | IP20 |
Mechanical life | |
operating cycles | 10 x 106 |
Contact material | AgNi-10 |
Mounting method | Mounting rail 35mm according to DIN EN 60715 TH35 |
Connection | Connection terminals |
Length of control cable | |
With conductor cross-section 0.75mm2 | 1000 m |
Safety contacts 17/18, 27/28, 37/38 | |
Number of safety contacts | 3 |
Auxiliary contacts S25/S26 | |
Number of auxiliary contacts | 1 |
Electrical connection ratings
Operating voltage | |
AC/DC | 24 V -10% ... +10% (All the electrical connections must either be isolated from the mains supply by a safety transformer according to EN 61558-2-6 with limited output voltage in the event of a fault, or by other equivalent isolation measures.) |
Rated insulation voltage Ui | 250 V |
Rated impulse withstand voltage Uimp | |
Leakage path/air gaps | 4 kV |
Overvoltage category according to IEC EN 60664-1 | 3 |
Reverse polarity protection | |
On version UB =24V DC | |
Connection rating | |
at 24V DC | 1,5 W |
Degree of contamination (external, according to EN 60947-1) | 2 |
Connection cross-section | 0,14 ... 2,5 mm² (Connection terminal (size)) |
Test voltage | |
Control system/contacts | 2,5 kV |
Control voltage | |
On S11 | 24 V |
Control current | |
S11...S14 | 40 mA |
LED indicator | 2 status displays (green) for relays K1 and K2 |
Safety contacts 17/18, 27/28, 37/38 | |
Type of output | |
NO | Relay contacts, floating, positively driven (redundant) (Positively driven relay according to EN 50205) |
Switching voltage | |
DC | max.24 V |
AC | max.250 V |
Switching current | min.20 mA at 24V |
Cumulative current | max.10,5 A For all contacts |
Fusing | |
External contact fuses (safety circuit) according to IEC 60269-1 | 10A gG |
Utilization category acc. to EN 60947-5-1 | |
AC-15 | 4A, 250V |
DC-13 | 2A, 24V |
AC-12 | 6A ohmic load, 250V |
DC-12 | 1.25A ohmic load, 24V |
Switching characteristics | Safety contacts with fixed time-delay |
Delay time | |
Fixed | 0,5 s |
Auxiliary contacts S25/S26 | |
Type of output | |
NC | As monitoring contact for safety relay |
Switching characteristics | Auxiliary contacts with fixed time-delay |
Other
In compliance with | EN ISO 13849-1: 2015; EN 62061: 2005 + AC: 2010 + A1: 2013 + A2: 2015; EN 50581: 2012 (RoHS) |
Reliability values according to EN ISO 13849-1
Performance Level | PL d (This value is dependent on the number of switching cycles and the switching current.) |
Category | 3 (This value is dependent on the number of switching cycles and the switching current.) |
PFHD | 1.03 x 10-7 (This value is dependent on the number of switching cycles and the switching current.) |
Number of switching cycles | |
≤ 0.1 A at 24 V DC | max.400000 1/Jahr |
≤ 1 A at 24 V DC | max.73000 1/Jahr |
≤ 2 A at 24 V DC | max.17000 1/Jahr |
Mission time | 20 y (This value is dependent on the number of switching cycles and the switching current.) |
Downloads
Complete package
Download all important documents with a single click.
Content:
- The operating instructions and any additions to the operating instructions or brief instructions
- Any data sheets to supplement the operating instructions
- The declaration of conformity
Single Documents
Declarations of conformity
EU-Konformitätserklärung
Doc. no.
Version
Language
Size
EU-Konformitätserklärung
Doc. no.
EDC2090791
Version
Language
Size
0,2 MB
UKCA-Konformitätserklärung
Doc. no.
Version
Language
Size
UKCA-Konformitätserklärung
Doc. no.
EDC20001502
Version
Language
Size
0,1 MB
Instructions
Operating Instructions Safety Contact Expansion ESM-TE3..
Doc. no.
Version
Language
Size
Operating Instructions Safety Contact Expansion ESM-TE3..
Mode d’emploi Extension de contacts de sécurité ESM-TE3..
Manual de instrucciones Ampliación de contactos de seguridad ESM-TE3..
Betriebsanleitung Sicherheits-Kontakterweiterung ESM-TE3..
Mode d’emploi Extension de contacts de sécurité ESM-TE3..
Manual de instrucciones Ampliación de contactos de seguridad ESM-TE3..
Betriebsanleitung Sicherheits-Kontakterweiterung ESM-TE3..
Doc. no.
2090075
Version
04/24
Language
Size
1,7 MB
Betriebsanleitung Sicherheits-Kontakterweiterung ESM-TE3..
Doc. no.
2090075
Version
04/24
Language
Size
0,7 MB
Other Documents
Approvals and certificates
CCC
Doc. no.
Version
Language
Size
CCC
Doc. no.
20001751
Version
Language
Size
0,0 MB
c UL us
Doc. no.
Version
Language
Size
c UL us
Doc. no.
Version
Language
Size
1,0 MB
c UL us
Doc. no.
Version
Language
Size
0,2 MB
Ordering data
Ordernumber | 097223 |
Item designation | ESM-TE301-05S |
Gross weight | 0,203kg |
Customs tariff number | 85364110 |
ECLASS | 27-37-18-19 Device for monitoring of safety-related circuits |