Basic device ESM-BA3.., 3 safety contacts, 1 auxiliary contact, cat. 4
- ESM-BA.. Use up to category 4 according to EN ISO 13849-1
- LED status indicators
- 1-channel or 2-channel control
- 3 redundant safety contacts
- 1 auxiliary contact (monitoring contact)
- Short circuit and earth fault/ground fault monitoring
- plug-in connection terminals
Description
Relay outputs
The outputs are electrically decoupled and of redundant design.
Connection options
By using suitable wiring, the following functions can be selected:
- Relay start with automatic start or a start button.
- Monitoring of downstream relays or contactors.
- Simultaneity monitoring to monitor safety components over time.
- Relay start using a monitored start button.
- Short circuit monitoring to detect short circuits between the connecting cables and to shut down the outputs or prevent relay starting if necessary.
- Earth fault/ground fault monitoring to detect short circuits between the connecting cables and earth or ground and to shut down the outputs or prevent relay starting if necessary.
Auxiliary contacts
The relays in the series ESM-BA3.. are available with electrically separate normally closed contacts and auxiliary contacts.
Important:
Depending on the device in question, a connection kit will be required.
Dimensional drawings
Connection examples
Technical data
Approvals
Mechanical values and environment
Housing material | |
Housing | Polyamide PA6.6 |
Weight | |
Net | 0,23 kg |
Ambient temperature | -15 ... 40 °C (If several ESM-BA3.. devices are closely spaced under load, the max. cumulative current at the ambient temperature of T=20°C is 9A; at T=30°C is 3A; at T=40°C is 1A. If these currents are exceeded, a spacing of 5mm between the devices must be observed.) |
Degree of protection | IP20 |
Mechanical life | |
operating cycles | 10 x 106 |
Contact material | AgSnO2 |
Mounting method | Mounting rail 35mm according to DIN EN 60715 TH35 |
Connection | Plug-in connection terminals |
Length of control cable | |
With conductor cross-section 0.75mm2 | 1000 m |
Safety contacts 13/14, 23/24, 33/34 | |
Number of safety contacts | 3 |
Auxiliary contacts 41/42 | |
Number of auxiliary contacts | 1 |
Electrical connection ratings
Operating voltage | |
AC/DC | 24 V -10% ... +10% (All the electrical connections must either be isolated from the mains supply by a safety transformer according to EN 61558-2-6 with limited output voltage in the event of a fault, or by other equivalent isolation measures.) |
Rated insulation voltage Ui | 250 V |
Rated impulse withstand voltage Uimp | |
Leakage path/air gaps | 4 kV |
Overvoltage category according to IEC EN 60664-1 | 3 |
Reverse polarity protection | |
On version UB =24V DC | |
Connection rating | |
at 24V DC | 2,3 W |
Degree of contamination (external, according to EN 60947-1) | 2 |
Connection cross-section | 0,14 ... 2,5 mm² (Connection terminal (size)) |
Test voltage | |
Control system/contacts | 2,5 kV |
Control voltage | |
On S11 | 24 V 18,6 ... 26 V Start button |
Control current | |
S11...S14 | 60 mA |
Breaking capacity | |
DC (for utilization category DC 13) | max.30 W |
Breaking capacity (VA) | |
AC | max.500 VA |
LED indicator | 2 status displays (green) for relays K1 and K2 |
Safety contacts 13/14, 23/24, 33/34 | |
Type of output | |
NO | Relay contacts, floating, positively driven (redundant) (Positively driven relay according to EN 50205) |
Switching voltage | |
AC | max.250 V |
DC | max.24 V |
Switching current | min.5 mA at 24V |
Cumulative current | max.15 A For all contacts (If several ESM-BA3.. devices are closely spaced under load, the max. cumulative current at the ambient temperature of T=20 °C is 9 A; at T=30 °C is 3 A; at T=40 °C is 1 A. If these currents are exceeded, a spacing of 5mm between the devices must be observed.) |
Fusing | |
External contact fuses (safety circuit) according to IEC 60269-1 | 10A gG |
Utilization category acc. to EN 60947-5-1 | |
AC-15 | 3A, 250V |
DC-13 | 3A, 24V |
AC-12 | 8A ohmic load, 250V (6 operating cycles/min.) |
DC-12 | 8A ohm resistive load, 40V (6 operating cycles/min.) |
Breaking capacity according to UL | 8 A, 250 V AC / 3 A, 24 V DC per contact |
Auxiliary contacts 41/42 | |
Type of output | |
NC | Relay contacts, floating |
Utilization category acc. to EN 60947-5-1 | |
AC-12 | 2A ohmic load, 250V |
DC-12 | 2 A ohm resistive load, 40V |
Breaking capacity according to UL | 2 A, 250 V AC / 2 A, 24 V DC per contact |
Other
In compliance with | EN ISO 13849-1: 2015; EN 62061: 2005 + AC: 2010 + A1: 2013 + A2: 2015; EN 50581: 2012 (RoHS) |
Reliability values according to EN ISO 13849-1
Performance Level | PL e (This value is dependent on the number of switching cycles and the switching current.) |
Category | 4 (This value is dependent on the number of switching cycles and the switching current.) |
PFHD | 1.2 x 10-8 (This value is dependent on the number of switching cycles and the switching current.) |
Number of switching cycles | |
≤ 0.1 A at 24 V DC | max.500000 1/Jahr |
≤ 1 A at 24 V DC | max.350000 1/Jahr |
≤ 2 A at 24 V DC | max.100000 1/Jahr |
Mission time | 20 y (This value is dependent on the number of switching cycles and the switching current.) |
Accessories
Downloads
Complete package
Download all important documents with a single click.
Content:
- The operating instructions and any additions to the operating instructions or brief instructions
- Any data sheets to supplement the operating instructions
- The declaration of conformity
Single Documents
Declarations of conformity
EU-Konformitätserklärung
Doc. no.
Version
Language
Size
EU-Konformitätserklärung
Doc. no.
EDC2090791
Version
Language
Size
0,2 MB
UKCA-Konformitätserklärung
Doc. no.
Version
Language
Size
UKCA-Konformitätserklärung
Doc. no.
EDC20001502
Version
Language
Size
0,1 MB
Instructions
Operating Instructions Safety Relay ESM-BA3..
Doc. no.
Version
Language
Size
Operating Instructions Safety Relay ESM-BA3..
Mode d’emploi Unité de base ESM-BA3..
Manual de instrucciones Módulo básico ESM-BA3..
Betriebsanleitung Basisgerät ESM-BA3..
Mode d’emploi Unité de base ESM-BA3..
Manual de instrucciones Módulo básico ESM-BA3..
Betriebsanleitung Basisgerät ESM-BA3..
Doc. no.
2090073
Version
04/24
Language
Size
1,7 MB
Betriebsanleitung Basisgerät ESM-BA3..
Doc. no.
2090073
Version
04/24
Language
Size
0,6 MB
사용 설명서 안전 릴레이 ESM-BA3..
Doc. no.
2090073
Version
04/24
Language
Size
0,8 MB
Other Documents
Application examples
Approvals and certificates
CCC
Doc. no.
Version
Language
Size
CCC
Doc. no.
20001751
Version
Language
Size
0,0 MB
TÜV Rheinland
Doc. no.
Version
Language
Size
TÜV Rheinland
Doc. no.
20001714
Version
Language
Size
0,6 MB
c UL us
Doc. no.
Version
Language
Size
c UL us
Doc. no.
Version
Language
Size
1,0 MB
c UL us
Doc. no.
Version
Language
Size
0,2 MB
Sales documents
Interrupteurs de sécurité à codage magnétique CMS
Doc. no.
Version
Language
Size
Interrupteurs de sécurité à codage magnétique CMS
Doc. no.
090606
Version
10-11/20
Language
Size
5,8 MB
Magnetically Coded Safety Switches CMS
Doc. no.
Version
Language
Size
Magnetically Coded Safety Switches CMS
Doc. no.
086824
Version
10-11/20
Language
Size
5,7 MB
Ordering data
Ordernumber | 097230 |
Item designation | ESM-BA301P |
Gross weight | 0,175kg |
European Article Number (EAN) | 4047048006003 |
Customs tariff number | 85364110 |
ECLASS | 27-37-18-19 Device for monitoring of safety-related circuits |