EUCHNER – More than safety.
EUCHNER – More than safety.

CMS-R-AZA-01PL-AS1 (Order no. 105090)

Non-contact safety switch CMS-R-AZA-01PL-AS1, with connecting cable and plug connector M12

  • Safety switches with integrated read head and integrated evaluation unit.
  • LED diagnostic displays
  • Operating distance 9 mm
CMS-R-AZA-01PL-AS1 (Order no. 105090)

Description

Actuator

An appropriate actuator to suit the read head selected is required. The dimensions of the actuators are the same as those of the read heads, although the former have no connecting cable.

AS-Interface inputs

D0 - D3

Switch actuated/open

Evaluation is performed via a safety monitor.

AS-Interface output

D1

LED 1 on read head (only CMS-R-AZA...)

LED function display

  • The ASI LED (dual LED red/green) displays the colors red, green and yellow. The status of the switch and the bus is indicated via this LED.
  • LED 1 can be connected via the AS-Interface bus, e.g. to indicate the door state.

Principle of operation

Reed contacts are installed in the read head of the safety system CMS. The contacts blades on the reed contacts will close when under the influence of the magnetic field from the actuator. The read head only responds to the specific mating component, that is a specific actuator that is allocated to the read head type.

Dimension drawing
Dimension drawing
Connector assignment
Connector assignment

Dimensional drawings

Dimensional drawings

Connection examples

Connection examples
View of connection side

Technical data

Approvals

EAC_RU C-DE.MO05.B.00971/20TUEV Süd München_Z10 10 07 40393 007c_UL_us_E155795_5/2Asi Interface_91301_

Workspace

Operating distance on min. 9 mm
Secured switch-off distance sar max. 70 mm
Center offset
symmetrical, at distance s = 3 mm 2.5 mm

Electrical connection values

ASI operating current max. 30 mA
ASI data in
according to AS-i Safety at Work D0, D1, D2, D3 (Switch actuated = code sequence / switch not actuated = zero sequence)
ASI data out
LED red D1 (1 = LED on)
AS-Interface LED
green Power
red Fault
AS-Interface slave type ID-Code: B, EA-Code: 7
ASI voltage
DC 26.5 ... 30 ... 31.6 V

Mechanical values and environment

Connection type hard-wired encapsulated cable with plug connector M12
Design A
Installation orientation any
Cable length 1 m
Mechanical life 100 x 10⁶
Response time
after change in the actuation status max. 5 ms
Degree of protection IP67
Ambient temperature -20 ... +60 °C
Material
Cable material PUR
Housing Reinforced thermoplastic (PPS), fully encapsulated
Method of operation magnetic, reed contact

Characteristic values according to EN ISO 13849-1 and EN IEC 62061

Mission time 20 y
Monitoring of the guard position
B10D 3 x 10⁶
Category 3
Performance Level PL e
PFHD 4.29 x 10-8

Miscellaneous

in compliance with EN 60947-5-3: 2013; EN ISO 13849-1: 2008; EN ISO 14119: 2013; EN 62026-2: 2013 (AS-i)

Downloads

Complete package

Download all important documents with a single click.

Content:

  • The operating instructions and any additions to the operating instructions or brief instructions
  • Any data sheets to supplement the operating instructions
  • The declaration of conformity
Download Complete Package (ZIP, 1,2 MB)

Single Documents

Other Documents

Ordering data

Ordernumber 105090
Item designation CMS-R-AZA-01PL-AS1
Gross weight 0,096kg
Customs tariff number 85389099990
ECLASS 27-27-24-02 Safety-related magnetic proximity switch

Technical support

Technical support
Do you have technical questions about our products, their possible use or applications? Our experts will be happy to help.

EUCHNER (UK) Ltd.
+44 114 2560123
sales(at)euchner.co.uk

EUCHNER USA Inc.
+1 315 701-0315
info(at)euchner-usa.com

Cookie notice

We use technically necessary cookies that are essential for the operation of the website. In addition, we use a statistics cookie to analyze the use of our website and to continuously improve our offer. You can decide for yourself whether you wish to consent to the use of the statistics cookie. Further information can be found in our privacy policy.