EUCHNER – More than safety.
EUCHNER – More than safety.

CKS-K-AS2A-U-C20-PC-123592 (Order no. 123592)

Key adapter CKS-K-AS with AS-i connection

  • Key adapter with integrated CES read head
  • Integrated diagnostic LEDs
  • Category 4 / PL e according to EN ISO 13849-1
  • Simple connection via AS-i
  • High degree of protection IP67
CKS-K-AS2A-U-C20-PC-123592 (Order no. 123592)

Description

Important: Keys must be ordered separately!

Dimension drawing
Dimension drawing
Wiring diagram
Wiring diagram

Dimensional drawings

Dimensional drawings
1LED
2Rubber seal
3Plug-in screw terminal

Connection examples

Connection examples

Technical data

Approvals

c_UL_us_E346349_1/1EAC_RU C-DE.HX37.B.14157/20Asi Interface_CKS-K-AS2A-.-C20-PC_

Electrical connection values

ASI operating current max. 50 mA
ASI data in
according to AS-i Safety at Work D2 (influenced by key)
according to AS-i Safety at Work D0 (influenced by key)
according to AS-i Safety at Work D1 (influenced by key)
according to AS-i Safety at Work D3 (influenced by key)
AS-Interface protocol ASi-3
AS-Interface slave type ID-Code: B, EA-Code: 0
ASI voltage 19 ... 31.6 V
Rated insulation voltage Ui 300 V
Rated impulse withstand voltage Uimp 1.5 kV
Turn-on time
Safety outputs max. 300 ms
Risk time according to EN 60947-5-3 max. 260 ms
Safety class III
Degree of contamination (external, according to EN 60947-1) 2

Mechanical values and environment

Connection type Screw terminal, 2-pin
Tightening torque
Fixing screws 0.25 ... 0.35 Nm
Installation orientation on the front
Mounting cut-out 33 x 68 mm
Shock and vibration resistance Acc. to EN IEC 60947-5-3
Degree of protection
in mounted condition (only access side) IP65/IP67 (on installation in flat metal plate, thickness = 2 mm)
Ambient temperature -10 ... +65 °C
Material
Housing PA6-GF30, black

Characteristic values according to EN ISO 13849-1 and EN IEC 62061

Mission time 20 y
Category 4
Performance Level PL e
PFHD 4.5 x 10-9

Miscellaneous

The following applies to the approval according to UL Operation only with UL Class 2 power supply or equivalent measures

Downloads

Complete package

Download all important documents with a single click.

Content:

  • The operating instructions and any additions to the operating instructions or brief instructions
  • Any data sheets to supplement the operating instructions
  • The declaration of conformity
Download Complete Package (ZIP, 2,5 MB)

Single Documents

Other Documents

Ordering data

Ordernumber 123592
Item designation CKS-K-AS2A-U-C20-PC-123592
Gross weight 0,18kg
Customs tariff number 85389099990
ECLASS 27-27-24-03 Safety-related transponder switch

Technical support

Technical support
Do you have technical questions about our products, their possible use or applications? Our experts will be happy to help.

EUCHNER (UK) Ltd.
+44 114 2560123
sales(at)euchner.co.uk

EUCHNER USA Inc.
+1 315 701-0315
info(at)euchner-usa.com

Cookie notice

We use technically necessary cookies that are essential for the operation of the website. In addition, we use a statistics cookie to analyze the use of our website and to continuously improve our offer. You can decide for yourself whether you wish to consent to the use of the statistics cookie. Further information can be found in our privacy policy.