Safety switch TP, plug connector M12, with door monitoring contact
- Auxiliary release on the front
- With door monitoring contact
- Increased horizontal overtravel
- Plug connector
Açıklama
Approach direction
Horizontal and vertical
Can be adjusted in 90° steps
Increased overtravel for horizontal approach direction
Solenoid operating voltage
- AC/DC 24 V +10%, -15%
Guard locking type
TP3 | Closed-circuit current principle, guard locking by spring force. Release by applying voltage to the guard locking solenoid. |
Switching element
4141 | Slow-action switching contact 2 NC + 2 NC (door monitoring contact) |
C1992
Direct connection to a safe bus module
Auxiliary release
This is used for releasing the guard locking with the aid of a tool. To protect against tampering, the auxiliary release is sealed with sealing lacquer.
Functional drawings
Dimensional drawings
1 | Auxiliary release |
2 | Locking screw |
Connection examples
Door monitoring | |
Solenoid monitoring |
Teknik Veriler
Approvals
Electrical connection values
Power consumption | 8 W |
Rated insulation voltage Ui | 30 V |
Rated impulse withstand voltage Uimp | 1.5 kV |
Utilization category | |
DC-13 | 1 A 24 V |
AC-15 | 1 A 24 V |
Short circuit protection according to IEC 60269-1 | 1A gG |
Solenoid operating voltage | |
AC/DC | 24 V -15% ... +10% |
Solenoid duty cycle | 100 % |
Switching voltage | |
min. at 10 mA | 12 V |
Switching current | |
min. at 24 V | 1 mA |
thermal rated current Ith | 1 A |
Mechanical values and environment
Approach speed | max. 20 m/min |
Connection type | |
1 x | Plug connector M12 (8-pin) |
Number of door position positively driven contacts | 1 |
Number of guard lock monitoring positively driven contacts | 2 |
Extraction force | 20 N |
Actuation frequency | max. 1200 1/h |
Actuating force | 10 N |
Installation orientation | any |
Mechanical life | 1 x 10⁶ |
Retention force | 10 N |
Switching principle | Slow-action switching contact |
Degree of protection | IP67 |
Ambient temperature | -20 ... +55 °C |
Material | |
Housing | Reinforced thermoplastic |
Contact | Silver alloy, gold flashed |
Locking force Fmax | 1300 N |
Locking force FZh | 1000 N |
Guard locking principle | Closed-circuit current principle |
Characteristic values according to EN ISO 13849-1 and EN IEC 62061
B10D | Mission time | |
---|---|---|
Monitoring of the guard position | 3x106 | 20 y |
Important! Values valid at DC-13 100 mA/24V | ||
Monitoring of guard locking | 3x106 | 20 y |
Important! Values valid at DC-13 100 mA/24V |
PL | Maximum SIL | Category | Mission time | |
---|---|---|---|---|
Control of guard locking | Depending on external control of guard locking | 20 y |
Miscellaneous
C number | |
C1992 | direct connection to safe bus module |
In combination with actuator ACTUATOR-P-GNT
Horizontal overtravel | 7 mm |
In combination with actuator ACTUATOR-P-GT
Horizontal overtravel | 2 mm |
Vertical overtravel | 1.5 mm |
Aksesuar
AE-K-A1-DULK1-84177
- Lock unique locking
- Key removable in “unlocked” and “locked” positions
AE-K-A1-IULK1-86236
- Identical locking
- Key removable in “unlocked” and “locked” positions
AE-K-A1-IUK2-109212
- Identical locking
- Key can be removed only in “unlocked” position
AE-K-A1-ILK1-121917
- Identical locking
- Key removable in “locked” position
AE-B-A1-02,0-096230
- Can be used as escape release or emergency release
- no automatic return
- Sheath length 2 m (rope length 6 m)
AE-B-A1-02,0-F-097747
- Can be used as escape release or emergency release
- automatic return
- Sheath length 2 m (rope length 6 m)
AE-B-A1-03,0-098313
- Can be used as escape release or emergency release
- no automatic return
- Sheath length 3 m (rope length 6 m)
AE-B-A1-04,0-098314
- Can be used as escape release or emergency release
- no automatic return
- Sheath length 4 m (rope length 6 m)
AE-B-A1-03,0-F-111233
- Can be used as escape release or emergency release
- automatic return
- Sheath length 3 m (rope length 6 m)
AE-B-A1-06,0-125582
- Can be used as escape release or emergency release
- no automatic return
- Rope length 6 m (without sheath)
AE-B-A1-06,0-F-124770
- Can be used as escape release or emergency release
- automatic return
- Rope length 6 m (without sheath)
RIEGEL 0 NP/TP OHNE RASTUNG
- Bolt for safety switch NP... and TP...A
- Steel bolt
- For doors hinged on the left or right
- Suitable for a door gap of approx. 6 mm
RIEGEL 1 NP/TP 1X RASTUNG ZU
- Bolt for safety switch NP...AS,TP...A and GP
- Steel bolt
- For doors hinged on the left or right
- Suitable for a door gap of approx. 15 mm
İndirme
Komple paket
Tüm önemli belgeleri tek bir tıklama ile indirin.
İçerik:
- Kullanım talimatları ve kullanım talimatlarına veya kısa talimatlara yapılan tüm eklemeler
- Kullanım talimatlarını tamamlayan tüm veri sayfaları
- Uygunluk beyanı
Tek Belgeler
Déclaration UE de conformité
Declaración de conformidad UE
EU-Konformitätserklärung
Dichiarazione UE di conformità
Déclaration UE de conformité
Declaración de conformidad UE
EU-Konformitätserklärung
Dichiarazione UE di conformità
Mode d’emploi Interrupteur de sécurité TP…
Manual de instrucciones Interruptor de seguridad TP…
Betriebsanleitung Sicherheitsschalter TP…
Diğer Belgeler
CAD Verileri
Sipariş verileri
Sip. No. | 087377 |
Makale adı | TP3-4141A024SM8C1992 |
Ağırlık | 0,473kg |
Gümrük sınıfı | 85365019000 |
ECLASS | 27-27-26-03 Safety switch with guard control |