EUCHNER – More than safety.
EUCHNER – More than safety.

GMOX-PR-12DN-C16 (Sip. No. 103267)

AS-Interface Safety at Work safety monitor with integrated Gateway GMOx

  • One AS-i master
  • Display and pushbuttons for diagnostics and adjustment
  • Memory card for different programs
  • Adjustable time-delay
  • 16 OSSDs
GMOX-PR-12DN-C16 (Sip. No. 103267)

Açıklama

Gateway to Profibus

For connection to a Profibus DP as a slave and as a master for an AS-i bus according to specification 3.0. Detection of ground shunt, double addressing and EMC problems.

Rapid setup with the display without PC. Direct display of faults with plain-text messages. Comprehensive AS-i diagnostics integrated. AS-i configuration software is available.

OSSDs (Output Signal Switching Devices), AS-i outputs

  • Two OSSDs with two redundant normally closed contacts each
  • Two OSSDs with semiconductor outputs
  • 12 additional safe AS-i outputs can be controlled

Inputs

  • 4 inputs, freely selectable

Logic functions

Programmable with AsiMon software. All safety components can be programmed with different functions as inputs. The inputs can be linked with AND or OR gates or via logic functions such as FlipFlop, switch-on delay, OFF time or pulses.

Different programs can be stored on a memory card.

AS-Interface monitor

The monitor controls two AS-i circuits with up to 62 safe slaves and up to 16 outputs.

Display and pushbuttons

The display is used to operate the gateway functionality as well as the monitor at the same time. The diagnostics and maintenance functions are considerably expanded compared to the SFM monitors. They can also be launched on the display without a PC monitor.

Incorporated security functions allow the programmed functionality to be protected and monitored.

Power supply

Type N permits connection of several GMOx devices to the same power supply unit.

Important: A connection kit must be ordered for each safety monitor. See Accessories.

Dimension drawing
Dimension drawing
Wiring diagram
Wiring diagram

Dimensional drawings

Dimensional drawings

Connection examples

Connection examples

Teknik Veriler

Approvals

EAC_RU C-DE.MO05.B.00971/20TUEV Nord_44 205 15102901_3528 6834c_UL_us_E323660_Asi Interface_83701_

Operating and display elements

Display LCD AS-i slave address indication, error messages
LED display
4 x LEDs, output circuits, state of the output circuits: LED off: open, LED on: closed
4 x LEDs EDM / start state of the inputs for the external device monitoring circuits: LED off: open, LED on: closed
LED AS-i active AS-i operation normal
LED U AS-i voltage OK
LED power, power supply ON
LED PROFIBUS master detected
LED config error configuration error
LED prj mode, configuration mode active
LED prg enable automatic slave programming possible
LED AUX auxiliary power is present
ItemColorExtrasSlide-in labelVersionNote slide-in labelSwitching elementNumberDesignation1LED
Pushbutton4

Electrical connection values

Power consumption 9 W
Connection cross section
for wire 2x (0.5...1.5) mm2
Flexible wire for cable end sleeve (2x (0.5...1.5) mm2)
(2x AWG 24 to 12)
Response delay
Safety circuit off max. 40 ms
ASI operating current max. 300 mA
ASI voltage 30 V
ASI cycle time 150 μs 150 x (number of slaves + 2)
Outputs
NumberTypeFunctionFootnote
4Output switching elements, output circuits 1, 2, 3 and 4Relay outputs 1.13, 2.13, semiconductor outputs 1.14, 2.14, 3.14, 4.14
Rated insulation voltage Ui 500 V
Inputs
NumberTypeFunctionFootnote
4Feedback loop/startEDM1/Start1: 1.Y1; EDM2/Start2: 2.Y1; EDM3/Start3:1.Y2; EDM4/ Start4: 2.Y2(EDM: external device monitor / feedback loop)
Switch-on delay 10 s
Card slot yes (Memory card to store the configuration data)

Mechanical values and environment

Number of OSSDs 16 (4 fed out)
Number of masters 1
Mounting type TH 35 mounting rail (EN IEC 60715)
Degree of protection IP20
Ambient temperature 0 ... +55 °C
Material
Housing Stainless steel
permissible shock and vibration load According to EN 61 131-2

Characteristic values according to EN ISO 13849-1 and EN IEC 62061

Mission time 20 y
Category 4
Performance Level PL e
PFHD 5.36 x 10-9
SIL CL 3

Miscellaneous

in compliance with EN 61 000-6-2, EN 61 000-6-4, EN 62 061, IEC 61 508, EN ISO 13 849-1

Interface

Bus data protocol PROFIBUS according to EN 50 170-3
Data rate 9.6 ... 12000 kbit/s
Date interface Serial interface RS 232
Periphery Decentralized peripheral equipment mapping of the AS-i slaves as I/O process data in the PROFIBUS; complete diagnostics and configuration via PROFIBUS DP master

İndirme

Komple paket

Tüm önemli belgeleri tek bir tıklama ile indirin.

İçerik:

  • Kullanım talimatları ve kullanım talimatlarına veya kısa talimatlara yapılan tüm eklemeler
  • Kullanım talimatlarını tamamlayan tüm veri sayfaları
  • Uygunluk beyanı
Paketin tamamını indirin (ZIP, 13,3 MB)

Tek Belgeler

Diğer Belgeler

Sipariş verileri

Sip. No. 103267
Makale adı GMOX-PR-12DN-C16
Ağırlık 0,936kg
Gümrük sınıfı 85371098
ECLASS 27-24-31-01 Configurable control component

Teknik Destek

Teknik Destek
Do you have technical questions about our products, their possible use or applications? Our experts will be happy to help.

EUCHNER End. Emn. Tek. Ltd. Sti.
+90 216 521-1000
info(at)euchner.com.tr

Çerez bildirimi

Web sitesinin çalışması için gerekli olan teknik olarak gerekli çerezleri kullanıyoruz. Buna ek olarak, web sitemizin kullanımını analiz etmek ve teklifimizi sürekli olarak iyileştirmek için bir istatistik çerezi kullanıyoruz. İstatistik çerezinin kullanımına izin vermek isteyip istemediğinize kendiniz karar verebilirsiniz. Daha fazla bilgiyi gizlilik politikamızda bulabilirsiniz.